C105.3 - Buildings Other than One- and Two-Family Dwellings, and Group R-3 Buildings.  


Latest version.
  • For all occupancies other than one- and two-family dwellings, and Group R-3 buildings, including commercial, industrial, multi-family dwellings, private schools, and institutions, fire hydrant spacing shall be 300 feet (91.44 m). No portion of lot frontage shall be more than 200 feet (60.96 m) from, via vehicular access, a public hydrant. No portion of a building shall be more than 400 feet (121.92 m) from, via vehicular access, a properly spaced public hydrant.

(Ord. 2017-0003 § 276, 2017.)