  • For one- and two-family dwellings, and Group R-3 buildings, fire hydrants shall be spaced no more than 600 feet (182.88 m) apart. For urban properties with more than one dwelling unit per acre, no portion of lot frontage should be more than 450 feet (137.16 m) away, via vehicular access, from a public hydrant. For non-urban properties less than one dwelling unit per acre, no portion of a structure shall be farther than 750 feet (228.6 m) away, via vehicular access, from a properly spaced public hydrant that meets the required fire-flow.

(Ord. 2017-0003 § 275, 2017.)