B105.1 - One- and Two-Family Dwellings, and Group R-3 Buildings.  


Latest version.
  • The minimum fire-flow and flow duration requirements for one- and two-family dwellings, and Group R-3 buildings shall be as specified in Tables B105.1(1) and B105.1(2).

    Exception: The minimum fire-flow for one- and two-family dwellings, and Group R-3 buildings located in a fire hazard zone shall not be less than 1,250 gallons (15,141.6 L/min) per minute.

(Ord. 2017-0003 § 258, 2017.)