B103.3 - Areas Without Water Supply Systems.
Parcels that are located outside the service boundary, above the existing pressure zone, or more than 2,000 lineal feet (609.6 m) from an existing water main of a water purveyor may provide an on-site water supply, when approved by the fire code official. For one-family dwellings the water supply shall be in accordance with Table B103.3. For other than one-family dwellings, the water supply shall be in accordance with NFPA 1142 or NFPA 13 water supply requirement, whichever is greater.
(Ord. 2017-0003 § 255, 2017.)
Table B103.3
Tank Sizes for One-Family DwellingsFire flow calculation area Tank size 0-3,600 square feet 13,000 gal 3,601-5,999 square feet 16,500 gal 6,000 square feet and greater 20,000 gal
(Ord. 2017-0003 § 256, 2017.)