B103.3 - Areas Without Water Supply Systems.  


Latest version.
  • Parcels that are located outside the service boundary, above the existing pressure zone, or more than 2,000 lineal feet (609.6 m) from an existing water main of a water purveyor may provide an on-site water supply, when approved by the fire code official. For one-family dwellings the water supply shall be in accordance with Table B103.3. For other than one-family dwellings, the water supply shall be in accordance with NFPA 1142 or NFPA 13 water supply requirement, whichever is greater.

    (Ord. 2017-0003 § 255, 2017.)

    Table B103.3
    Tank Sizes for One-Family Dwellings

    Fire flow calculation area Tank size
    0-3,600 square feet 13,000 gal
    3,601-5,999 square feet 16,500 gal
    6,000 square feet and greater 20,000 gal

     

(Ord. 2017-0003 § 256, 2017.)