§ 910.4.4. Activation.  


Latest version.
  • The mechanical smoke removal system shall be activated by manual controls only. For basement level enclosed parking garages, mechanical smoke removal systems shall be automatically activated by the automatic sprinkler system or by heat detectors having operating characteristics equivalent to those described in Section 910.3. Individual manual controls for each fan unit shall also be provided.

(Ord. 2017-0003 § 164, 2017.)