§ 905.2.1.2. Fire Department Connection.  


Latest version.
  • Standpipes shall be equipped with a listed four-way Fire Department connection. Systems with three or more standpipes shall be provided with a sufficient number of inlets as required by the fire code official. All Fire Department connections shall be located on the building address street front, not less than 24 inches (609.6 mm) or more than 42 inches (1066.8 mm) above grade and shall be equipped with an approved straight-way check valve and substantial plugs or caps. All Fire Department connections shall be visible, accessible, and clearly marked with approved signage. More than one Fire Department connection may be required. Fire Department connection location shall meet the requirements in Section 912.2.1.

(Ord. 2017-0003 § 144, 2017.)