§ 2305.5. Hold-down connectors.  


Latest version.
  • In Seismic Design Category D, E or F, hold-down connectors shall be designed to resist shear wall overturning moments using 75 percent of the allowable seismic load values. Such values shall be established in a valid research report from approved sources or by accepted engineering practice and the provisions of this Code.

    Exception: Values established by specialized cyclic and dynamic testing may be used when approved by the Building Official in accordance with Section 104.2.8.

    Connector bolts into wood framing shall require steel plate washers on the post on the opposite side of the anchorage device. Plate size shall be a minimum of 0.229 inches by 3 inches by 3 inches (5.82 mm by 76 mm by 76 mm) in size. Hold-down connectors shall be tightened to finger tight plus one half (1/2) wrench turn just prior to covering the wall framing.