J109.1 - General.  


Latest version.
  • Unless otherwise recommended by a licensed Civil Engineer and approved by the Building Official, drainage facilities and terracing shall be provided in accordance with the requirements of Section J109.2 for all cut and fill slopes 3 units horizontal to 1 unit vertical (33-percent slope) and steeper.

    For slopes flatter than 3 units horizontal to 1 unit vertical (33-percent slope) and steeper than 5 units horizontal to 1 unit vertical (20-percent slope) a paved swale or ditch shall be installed at 30 foot (9.1 m) vertical intervals to control surface drainage and debris. Swales shall be sized based on contributory area and have adequate capacity to convey intercepted waters to the point of disposal as defined in Section J109.5. Swales must be paved with reinforced concrete not less than 3 inches (0.08 m) in thickness, reinforced with 6-inch (0.2 m) by 6-inch (0.2 m) No. 10 by No. 10 welded wire fabric or equivalent reinforcing centered in the concrete slab or an equivalent approved by the Building Official. Swales must have a minimum flow line depth of 1 foot (0.3 m) and a minimum paved width of 18 inches (0.5 m). Swales shall have a minimum gradient of not less than 5 percent. There shall be no reduction in grade along the direction of flow unless the velocity of flow is such that slope debris will remain in suspension on the reduced grade.